PCC Panels & LV Board Range: Products and How to Choose

Main LV switchboards, PCCs, distribution boards, meter boards and data-centre panels built to IEC 61439, Form 1 to Form 4, up to 6300 A.

Low-voltage (LV) switchgear and Power Control Centre (PCC) panels are factory-built assemblies that take power from a transformer or generator and distribute it through busbars and protective devices to downstream circuits at up to 1,000 V AC. They are governed by IEC 61439-1 and -2 and serve Kenyan factories, hospitals, commercial buildings and data centres.

Panel Tech Systems builds this range in Nairobi to IEC 61439, with routine-tested assemblies supplied with full documentation and test reports. It covers the main LV Panel (100 A to 6300 A, Form 1 to Form 4 construction), Distribution Boards, Meter Boards, Protection Panels, Panels For Data Centers with dual incomers and bus-section arrangements, Feeder Pillar Panels for outdoor distribution, and Motor Control, Starter Panels and PLC Automation Panels for process loads. Assemblies use ABB, Schneider, Siemens or Chint components, and IP54 and IP65 enclosures are available. For design, manufacture and on-site commissioning, see our low voltage panel service; for plants with heavy motor and process loads, see our manufacturing solutions.

Products in this Range

Distribution Boards
Low Voltage Panels

Distribution Boards

Distribution boards divide the main electrical power supply into smaller circuits while providing circuit protection for residential, commercial and industrial applications.

View Details
LV Panel Low Voltage Panels
Low Voltage Panels

LV Panel

High-quality low voltage panels designed for reliable power distribution and protection in industrial and commercial installations.

View Details
Meter Boards Low Voltage Panels
Low Voltage Panels

Meter Boards

Meter boards house electricity meters, circuit breakers, fuses and other protective devices for proper monitoring and regulation of electrical supply.

View Details
Motor Control Low Voltage Panels
Low Voltage Panels

Motor Control

Reliable motor control panels for industrial and commercial use, providing customised solutions for safe and efficient motor operation.

View Details
PLC Automation Panels
Low Voltage Panels

PLC Automation Panels

Advanced PLC automation panels for intelligent control of industrial processes, tailored to your operational requirements.

View Details
Protection Panels
Low Voltage Panels

Protection Panels

Robust protection panels safeguarding electrical systems and equipment from faults, overloads and short circuits.

View Details
Starter Panels Low Voltage Panels
Low Voltage Panels

Starter Panels

Motor starter panels for safe starting and stopping of industrial motors with overload and short circuit protection.

View Details
Panels For Data Centers
Low Voltage Panels

Panels For Data Centers

Specialised low voltage panels designed for data centre power distribution, ensuring high reliability and redundancy.

View Details
Feeder Pillar Panels
Low Voltage Panels

Feeder Pillar Panels

Feeder pillar panels providing reliable power distribution solutions for outdoor and indoor industrial and commercial applications.

View Details

LV assemblies in the Panel Tech range: role, governing standard and the key data to specify

Product Role in the system Standard Typical location Key data to specify
LV Panel (main switchboard / PCC) Takes transformer/generator supply; feeds large feeders and sub-boards IEC 61439-1 and -2 Main switchroom near the transformer InA, Icw/Ipk, Form, IP, incomer arrangement
Distribution Boards Split supply into sub-circuits and final circuits IEC 61439-3 (ordinary persons) or IEC 61439-2 Floors, zones and plant areas Number of ways, incomer rating, RCD requirements
Meter Boards House utility meters or sub-meters with protection IEC 61439 series plus utility requirements Supply intake, tenant risers Number of meters, direct or CT metering
Protection Panels Relays detect faults and trip the switchgear IEC 61439-2 (LV); relays to IEC 60255 Switchrooms and substations Protection functions, CT ratios, trip supply
Panels For Data Centers Redundant distribution for UPS and IT loads IEC 61439-1 and -2 UPS rooms and data halls Dual incomers, bus section, circuit metering, Form
Feeder Pillar Panels Outdoor distribution to external loads IEC 61439-5 (public networks) or IEC 61439-2 Outdoors, plinth- or pole-mounted IP and IK ratings, ways, vandal resistance
Motor Control / Starter Panels Start, stop and protect motors IEC 61439-2; starters to IEC 60947-4-1 Plant rooms, pump houses Motor kW, starting method, coordination type
PLC Automation Panels Automate machine and process sequences IEC 61439-2; PLCs to IEC 61131 Beside the process or MCC I/O count, PLC platform, communications

How to Choose: LV Switchgear & PCC Panels

1. Decide which board you actually need

Start from the single-line diagram. The main switchboard or PCC takes the transformer and generator incomers and feeds the large loads and sub-boards. Distribution Boards split the supply into final circuits, while Meter Boards, Protection Panels and data-centre panels are specialised assemblies. Groups of motor feeders are usually better placed in a dedicated motor control panel than in the PCC.

2. Fix the rated currents

State the rated current of the assembly (InA), of each outgoing circuit (Inc) and, where loads do not all run at full current together, the rated diversity factor (RDF). IEC 61439 ratings assume normal service conditions: indoor ambient air not exceeding 40 °C, with a 24-hour average not exceeding 35 °C, at altitudes up to 2,000 m. Hotter switchrooms, and the highland sites in Kenya that lie above 2,000 m, need derating agreed with the builder.

3. Match the short-circuit rating to the fault level

The prospective fault current at the panel depends mainly on transformer size and impedance, any generator contribution and the cable run to the board. The busbar system's rated short-time withstand current (Icw, stated with a duration, commonly 1 s) must be at least the prospective RMS fault current, and its rated peak withstand current (Ipk) at least the corresponding peak. Each protective device's breaking capacity must be at least the fault level where it is installed, unless the manufacturer's published back-up protection tables apply. Our guide to short-circuit ratings for switchboards explains the calculation.

4. Specify the Form of internal separation

Form 1 has no internal separation. Forms 2, 3 and 4 progressively separate the busbars, functional units and outgoing terminals, and the "a" and "b" variants define how the terminals are separated. Choose the Form by who will work on the board and what must stay energised during maintenance, as set out in Form 1 to Form 4 LV panel construction.

5. Set IP and IK ratings for the location

Degree of protection is stated as an IP code to IEC 60529, and impact resistance as an IK code to IEC 62262. A clean, ventilated switchroom needs far less than a dusty factory floor or an outdoor plinth. A higher IP rating also reduces natural cooling, so it affects the current rating.

6. Plan incomers, changeover and metering

Decide whether the board needs a single incomer, dual incomers with a bus coupler, or an integrated generator changeover section (see ATS / MTS Kenya). Add power factor correction, such as a PFC panel, where low power factor attracts utility charges, and fit multifunction metering on incomers and major feeders. Data halls and other continuous loads usually need redundant supply paths; see our data centre power solutions.

7. Ask for the verification evidence

IEC 61439 requires design verification of the assembly design (by testing, comparison with a verified reference design, or assessment) and routine verification of every panel built. Ask for both in the submittal, together with the GA drawing, single-line diagram and component schedule.

Ready to specify? Send your single-line diagram, load schedule and site conditions through our contact form or call 0799 531765 for a quotation.

Technical Guides

Form 1 to Form 4 LV Panel Construction: An Engineer's Selection Guide

IEC 61439-2 Forms 1 through 4 define how busbars, functional units, and outgoing terminals are separated inside an LV panel. The form you specify controls maintenance access, fault containment, and operational safety. This guide explains each Form, when to use which, and the cost trade-offs.

Read guide

Short Circuit Rating for Switchboards in Kenya: 2026 Engineering Guide and Specs | Paneltech Systems Kenya

Looking for the correct short circuit rating for switchboards in Kenya? Learn when 25kA, 36kA, 50kA, or 65kA fault ratings are appropriate and why proper fault studies matter. Get an engineered switchboard from Paneltech Systems Ltd.

Read guide

IP Rating for Electrical Panels Kenya: 2026 Engineering Guide and Specs | Paneltech Systems Kenya

Looking for the right IP rating for electrical panels Kenya projects require? Learn when to use IP42, IP54, IP55, IP65, and IP66 for dusty factories, coastal installations, and outdoor switchboards. Get an engineered enclosure from Paneltech Systems Ltd.

Read guide

IEC 61439 Compliance Kenya: 2026 Engineering Guide and Specs | Paneltech Systems Kenya

Looking for IEC 61439 compliance Kenya projects require? Learn why design verification, temperature-rise testing, short-circuit strength, and compliant switchboard construction matter. Talk to Paneltech Systems before approving your next LV panel.

Read guide

Model BOQ Clauses for LV Switchboards: Kenya Specification Guide

A practical specification resource for consultants, contractors and procurement teams preparing BOQs for LV switchboards. The clauses cover ratings, construction, protection, enclosure requirements, testing, documentation and standards to help reduce non-compliant bids.

Read guide

Breaker Discrimination Kenya: Why One Faulty Circuit Should Never Trip the Main

Breaker discrimination Kenya ensures faults stay local by coordinating circuit breakers for safe, reliable power distribution. Discover how selectivity, trip curves, MCCB and ACB coordination improve uptime in industrial and commercial electrical systems.

Read guide

Frequently Asked Questions: LV Switchgear & PCC Panels

The terms overlap in Kenyan practice. A Power Control Centre (PCC), or main LV switchboard, takes the incoming supply from the transformer and generator, usually through air circuit breakers or large MCCBs, and distributes it to large feeders and sub-boards. A main distribution board (MDB) does the same job inside a building, often at a lower current. Sub-distribution boards and final distribution boards then feed individual floors, zones and circuits. All of them are low-voltage assemblies covered by the IEC 61439 series.
It depends on maintenance and continuity needs. Form 1 (no internal separation) is common in small sub-boards. Form 2 separates the busbars from the functional units. Form 3 also separates functional units from each other, so one feeder can be isolated and worked on while neighbouring feeders stay live, subject to safe isolation procedures. Form 4 additionally separates the outgoing terminals of each functional unit from those of the others, and is typically chosen for hospitals, data centres and critical process plant. Higher Forms add size and cost, so specify them where they are genuinely needed.
First calculate the prospective short-circuit current at the panel location. It depends mainly on the transformer rating and impedance, any generator contribution, and the size and length of cable between the transformer and the board. The busbar system's rated short-time withstand current (Icw) must be at least the prospective RMS fault current and its peak withstand current (Ipk) at least the corresponding peak, and every protective device must be able to break the fault level where it is installed. State the figures on the single-line diagram. Boards close to large transformers need the highest ratings.
Choose by location. Indoor boards in clean, dry, ventilated switchrooms are often specified at a modest level such as IP31 or IP41. Dusty factories and humid sites usually call for IP54, and outdoor or wash-down locations need higher ratings such as IP65, often with an IK impact rating to IEC 62262. Sealing a panel more tightly reduces heat dissipation, so the builder must verify temperature rise at the chosen IP rating. Panel Tech Systems offers IP54 and IP65 enclosures.
Not exactly. "Type-tested assembly" (TTA) is terminology from the older IEC 60439, which IEC 61439 has replaced. IEC 61439 instead requires design verification of the assembly design, by testing, comparison with a verified reference design or assessment depending on the characteristic, plus routine verification of every panel produced. When buying, ask for the design verification evidence for the switchboard system and the routine verification report for your specific panel, rather than accepting a general "type-tested" claim.
Yes. The LV Panel can be configured with an integrated ATS section on the incoming side, which avoids a separate changeover cabinet where the transfer switch feeds the same busbar as the main switchgear. Open- and closed-transition sections are available. Transfer switching equipment is covered by IEC 60947-6-1. In an open-transition scheme, mechanical and electrical interlocking must prevent the utility and generator supplies from ever being connected together; closed transition briefly parallels the sources, so it needs synchronising control and the utility's agreement. Standalone units are also available as ATS / MTS Kenya.
Panel Tech Systems builds LV panels with components from ABB, Schneider, Siemens and Chint. The brand is normally set by the project specification or the consultant's approved list. Keeping upstream and downstream breakers within one manufacturer's range makes it easier to confirm selectivity from that manufacturer's published tables, so mixed-brand boards need extra checking. Our guide to breaker discrimination explains why this matters.
Send the single-line diagram and load schedule, the incoming supply details (transformer kVA and any generator), the required short-circuit rating, Form of separation and IP rating, metering requirements, preferred breaker brand, cable entry (top or bottom), and the space and access available on site. The more complete the information, the more accurate the quotation. Our guide on what to send for an accurate quotation has a full checklist, or call 0799 531765.