Energy Meters, Protection Relays and CTs for LV Panels in Kenya

Multispan, Rishabh and Elmeasure meters, current transformers, voltage and earth leakage relays for LV panels, plus a guide to CT class and Modbus.

Smart components are the measuring, monitoring and protection devices mounted inside low-voltage panels: multifunction and energy meters, current transformers (CTs), and voltage, phase and earth leakage relays. Measuring CTs are specified to IEC 61869-2 and energy-meter accuracy to IEC 62053. In Kenya they are used for sub-metering, motor protection and energy monitoring in factories, commercial buildings and pump stations.

Panel Tech Systems supplies Multispan smart components, Rishabh meters and current transformers (solid-core, and split-core for retrofits) and Elmeasure energy management products, with select Schneider, ABB and Siemens equivalents where a plant standard calls for them. Our engineers configure Modbus RTU/TCP communication so readings reach your BMS or SCADA, and supply the Modbus mapping documentation. For panel integration and commissioning, see our smart components service; for factory energy monitoring, see manufacturing and industrial.

Products in this Range

AMP 19 Smart Components
Smart Components

AMP 19

Multispan AMP 19 ÔÇö advanced power monitoring and measurement instrument for industrial applications.

View Details
AVH-16-M1 Smart Components
Smart Components

AVH-16-M1

Multispan AVH-16-M1 voltage protection relay for reliable protection of electrical equipment against voltage faults.

View Details
CMS 5X Smart Components
Smart Components

CMS 5X

Multispan CMS 5X current monitoring relay for accurate current measurement and protection in industrial systems.

View Details
DI 22U Smart Components
Smart Components

DI 22U

Multispan DI 22U digital indicating instrument for clear and precise display of electrical parameters.

View Details
DI-22 Smart Components
Smart Components

DI-22

Multispan DI-22 digital display instrument providing accurate measurement and indication of electrical values.

View Details
Elmeasure Smart Components
Smart Components

Elmeasure

Elmeasure smart energy meters for comprehensive energy monitoring, measurement and management in commercial and industrial settings.

View Details
ELR 63 Smart Components
Smart Components

ELR 63

Multispan ELR 63 earth leakage relay for detecting and protecting against earth fault currents in electrical installations.

View Details
EPM-14-M1 Smart Components
Smart Components

EPM-14-M1

Multispan EPM-14-M1 energy and power meter providing accurate measurement of energy consumption parameters.

View Details
LC 1046D Smart Components
Smart Components

LC 1046D

Multispan LC 1046D level controller for reliable liquid level monitoring and control in industrial processes.

View Details
MFM 13 Smart Components
Smart Components

MFM 13

Multispan MFM 13 multifunction meter for simultaneous measurement of multiple electrical parameters in one compact unit.

View Details
MFM 14DC Smart Components
Smart Components

MFM 14DC

Multispan MFM 14DC DC multifunction meter designed for accurate measurement in DC power systems and renewable energy installations.

View Details
MI 431 Smart Components
Smart Components

MI 431

Multispan MI 431 insulation monitoring relay for continuous monitoring of insulation resistance in isolated power systems.

View Details
MPD 192 Smart Components
Smart Components

MPD 192

Multispan MPD 192 motor protection device providing comprehensive protection for three-phase motors against faults.

View Details
MS 1248u Smart Components
Smart Components

MS 1248u

Multispan MS 1248u dual timer relay offering flexible timing functions for industrial control and automation applications.

View Details
Multispan Smart Components
Smart Components

Multispan Smart Components

Multispan smart meters, relays and measurement instruments for intelligent power monitoring in industrial environments.

View Details
PI 38 Smart Components
Smart Components

PI 38

Multispan PI 38 power factor indicator providing accurate real-time display of power factor in electrical systems.

View Details
POD 22 Smart Components
Smart Components

POD 22

Multispan POD 22 phase-over and under voltage relay for protection against phase voltage anomalies.

View Details
PS24-5A Smart Components
Smart Components

PS24-5A

Multispan PS24-5A 24V DC power supply providing stable and reliable DC power for control circuits and instruments.

View Details
PSR-22 Smart Components
Smart Components

PSR-22

Multispan PSR-22 phase sequence relay ensuring correct phase rotation and protecting motors from phase reversal.

View Details
RS 40A Smart Components
Smart Components

RS 40A

Multispan RS 40A residual current relay for sensitive earth fault detection and protection in power systems.

View Details
SD 22 Smart Components
Smart Components

SD 22

Multispan SD 22 star-delta timer relay for automatic star-delta motor starting to reduce inrush current.

View Details
SPP-22 Smart Components
Smart Components

SPP-22

Multispan SPP-22 single phase protection relay guarding single-phase equipment against voltage and frequency faults.

View Details
SVR-22 Smart Components
Smart Components

SVR-22

The SVR-22 is an advanced voltage regulator designed to ensure stable and reliable voltage levels, protecting sensitive equipment from voltage fluctuations.

View Details
UTC 221G Smart Components
Smart Components

UTC 221G

Multispan UTC 221G universal timer counter for precise timing and counting operations in industrial control applications.

View Details
UTC 3202 Smart Components
Smart Components

UTC 3202

Multispan UTC 3202 timer relay with multiple timing modes for versatile control applications in industrial automation.

View Details
UTR 2033 Smart Components
Smart Components

UTR 2033

Multispan UTR 2033 under and over voltage relay providing reliable protection against voltage deviations in power systems.

View Details
V22-RYB Smart Components
Smart Components

V22-RYB

Multispan V22-RYB three-phase voltage indicator providing clear visual indication of phase voltages in panel boards.

View Details
VAF 16 Smart Components
Smart Components

VAF 16

Multispan VAF 16 volt-amp-frequency meter for simultaneous measurement of voltage, current and frequency parameters.

View Details
VAW 34DC Smart Components
Smart Components

VAW 34DC

Multispan VAW 34DC DC volt-amp-watt meter for accurate measurement in DC electrical systems and solar installations.

View Details
VMR-13 Smart Components
Smart Components

VMR-13

The VMR-13 Voltage Monitoring Relay ensures the stability and safety of power distribution networks, protecting against voltage anomalies.

View Details
VPR 22 Smart Components
Smart Components

VPR 22

Multispan VPR 22 voltage protection relay providing comprehensive protection against over-voltage and under-voltage conditions.

View Details
VPR-126 Smart Components
Smart Components

VPR-126

Multispan VPR-126 advanced voltage protection relay with extended protection functions for demanding industrial applications.

View Details
VPR-3P Smart Components
Smart Components

VPR-3P

The VPR-3P three-phase voltage protection relay safeguards electrical systems against voltage anomalies and phase faults.

View Details
WLC-22 Smart Components
Smart Components

WLC-22

Multispan WLC-22 water level controller providing automated level control for tanks and pumping systems.

View Details
3 Phase Current Transformer
Rishabh Products

3 Phase Current Transformer

3-Phase Current Transformers for accurate power monitoring and measurement. Paneltech Systems offers high-quality Rishabh 3-Phase CTs for industrial energy monitoring and protection.

View Details
3 Phase RJ12 Rishabh Products
Rishabh Products

3 Phase RJ12

3-Phase RJ12 from Paneltech Systems for accurate power monitoring and efficient current measurement in industrial applications.

View Details
Rish LM 1360 Rishabh Products
Rishabh Products

Rish LM 1360

The Rish LM 1360 from Paneltech Systems offers advanced power monitoring and measurement solutions for precise energy usage tracking in industrial settings.

View Details
Rishabh CTs Rishabh Products
Rishabh Products

Rishabh CTs

Rishabh current transformers ÔÇö precision measurement instruments for accurate current sensing in power metering and protection applications.

View Details
Rishabh Splitcore
Rishabh Products

Rishabh Splitcore

Rishabh Split Core CTs from Paneltech Systems offer easy installation and accurate power monitoring without disconnecting cables.

View Details
Single Phase RJ12 CT
Rishabh Products

Single Phase RJ12 CT

Single Phase RJ12 current transformer for precise single-phase current measurement in power monitoring and metering applications.

View Details

Smart component types compared: what each does, what to specify and the reference standard

Device What it does Key specs to check Reference standard Examples in our range
Solid-core CT Steps line current down to 1 A or 5 A Ratio, accuracy class, VA burden, window size IEC 61869-2 Rishabh CTs; 3 Phase Current Transformer
Split-core CT Same job; opens to clamp round existing cable Window size, ratio, accuracy class IEC 61869-2 (check datasheet) Rishabh Splitcore
AC multifunction meter Measures V, A, kW, kVAr, PF, Hz and kWh Accuracy class, CT input, Modbus RTU, harmonics IEC 61557-12; IEC 62053-21/-22 MFM 13; Elmeasure
DC meter Measures DC voltage, current, power and energy DC voltage range, current sensing method Product datasheet MFM 14DC; VAW 34DC
Voltage / phase protection relay Trips on phase loss, wrong sequence, under/over voltage Voltage band, time delay, contact rating Product datasheet VPR-3P; VPR 22; VPR-126
Earth leakage relay with core-balance CT Detects residual current; trips contactor or shunt trip Sensitivity (mA), time delay, CBCT diameter IEC 60947-2 Annex M ELR 63
24 V DC power supply Powers control circuits, relays and instruments Output current with margin, input voltage Product datasheet PS24-5A

How to Choose: Smart Components

1. Decide what the device must do

Start with the job, not the catalogue. Measurement (sub-metering, energy audits, tenant recharge) needs a meter plus matching CTs. Protection (phase failure, voltage band, earth leakage) needs a relay with an output contact wired into a contactor coil or breaker shunt trip. Control support (timers, level control, 24 V DC supply) sits alongside both. Many panels need all three.

2. Size the current transformers

  • Ratio: choose a primary rating so normal load sits in the upper part of the CT range. A 400/5 CT on a feeder that normally carries 40 A will read poorly.
  • Accuracy class (IEC 61869-2): class 0.5 or 1 suits most monitoring. The S classes (0.2S, 0.5S) have accuracy limits specified down to 1% of rated current, rather than 5% for the standard classes, which helps on loads that vary widely. Protection CTs (5P, 10P) are a different product and should not be used to feed energy meters.
  • Secondary and burden: 5 A is common, but on long lead runs a 1 A secondary cuts lead burden by a factor of 25. Add up the meter and lead burden in VA and keep it within the CT rating.
  • Solid or split core: solid-core CTs suit new boards; Rishabh Splitcore CTs clamp around existing cables for retrofits. Our guide to the role of CTs in power measurement covers the basics.

Never open-circuit the secondary of a CT while primary current flows. Wire CTs through shorting test terminals so a meter can be removed safely.

3. Match the meter accuracy to the purpose

Energy accuracy classes come from IEC 62053-21 (e.g. Class 1) and IEC 62053-22 (0.2S, 0.5S); multifunction power metering and monitoring devices (PMDs) are covered by IEC 61557-12. Class 1 is typical for internal sub-metering; incomers and recharge points often justify 0.5S. Overall accuracy is limited by the weakest link, so a 0.5S meter on a class 1 CT does not give 0.5S results. If the site runs VFDs or large UPS loads, choose a meter that reports harmonics. A three-phase multifunction meter such as the MFM 13 covers voltage, current, power, power factor, frequency and energy in one unit.

4. Plan communication early

Modbus RTU over RS-485 is the usual choice for meters reporting to a PLC, BMS or energy dashboard. Daisy-chain the devices (no star wiring), terminate both ends of the line, give each meter a unique address (1-247) and set the same baud rate and parity on all of them. A standard RS-485 segment supports 32 unit loads before a repeater is needed. Ask for the register map before ordering so the integrator can confirm the parameters you need are available.

5. Choose relay functions for the risk

  • Motors and pumps: a three-phase voltage protection relay such as the VPR-3P trips on phase loss, wrong phase sequence and under or over voltage before the motor overheats. Our article on motor protection relay settings explains overload and phase-failure settings.
  • Earth leakage: an earth leakage relay like the ELR 63 works with a core-balance CT placed around all live conductors, neutral included, never the protective earth. Adjustable sensitivity and time delay allow coordination between upstream and downstream devices.
  • Contacts: check the relay output contact rating against the coil it switches, and whether you need fail-safe (normally energised) operation.

6. Check the panel itself

Confirm DIN-rail or door cut-out space, auxiliary supply voltage, and ventilation: meters and relays are electronic and dislike hot, dusty switchrooms. If the panel is being built new, metering and relays should be designed into the IEC 61439 assembly, not added later.

Get a quote

Send us your single-line diagram or a list of feeders with their normal load currents, and tell us whether you need monitoring, protection or both. Our engineers will propose matched meters, CTs and relays. Request a quote or call 0799 531765.

Technical Guides

Current Transformers Kenya: The Role of CTs in Power Measurement

Current Transformers (CTs) scale down high electrical currents into safe, measurable values for meters. They enable accurate power monitoring and protection in industrial electrical systems.

Read guide

Rishabh vs Elmeasure: Energy Meter Comparison Kenya

Rishabh vs Elmeasure compared for accuracy, communication protocols, energy monitoring, power-quality measurement and technical support. Learn how to select the right metering range for Kenyan electrical panels.

Read guide

Energy Monitoring Panel Kenya: 2026 Engineering Guide and Specs | Paneltech Systems Kenya

Looking for an energy monitoring panel Kenya businesses trust? Learn how Modbus meters, sub-metering, per-feeder kWh monitoring, and intelligent dashboards help reduce electricity costs. Get a custom metering panel from Paneltech Systems Ltd.

Read guide

Motor Protection Relay Settings Kenya Explained: Overload, Phase Failure

Learn the correct motor protection relay settings for overload, phase failure, and stall trips in Kenya. This guide explains IEC-compliant settings, commissioning best practices, and motor protection for reliable industrial operations.

Read guide

Splitcore CTs Kenya: The Easiest Way to Install Energy Monitoring in Existing Buildings

Splitcore CTs use a snap-on design to install around live cables without disconnection. They enable fast, low-disruption energy monitoring upgrades in existing buildings.

Read guide

ELR 63 Kenya: Understanding Earth Leakage with the ELR 63 Relay

The ELR 63 earth leakage relay detects leaking current and trips the circuit to prevent electric shock and fire risks. It enhances safety by instantly disconnecting faulty electrical systems.

Read guide

Frequently Asked Questions: Smart Components

Pick a CT whose primary rating is just above the maximum expected load current of the feeder, so normal load sits in the upper part of the CT range. A feeder that peaks at about 90 A would typically use a 100/5 CT, not a 400/5. Oversized CTs read poorly at light load. Program the same ratio into the meter, because a wrong ratio setting scales every reading by the wrong factor. If load varies widely, consider an S-class CT (0.5S): its accuracy limits are specified down to 1% of rated current rather than 5%.
Both are standard. 5 A is the most common and suits meters mounted close to the CTs, for example on the same panel door. Where the meter is far from the CTs, a 1 A secondary is better: for the same leads, the I squared R burden of the wiring is 25 times lower, so the CT is less likely to be overloaded and lose accuracy. Whichever you choose, the meter's current input must match the CT secondary, and the total burden of meter plus leads must stay within the CT's VA rating.
For internal cost allocation, Class 1 active-energy accuracy (IEC 62053-21) is widely used. For main incomers or where readings are used to recharge tenants, Class 0.5S (IEC 62053-22) is a common specification. Remember the CTs count too: pair a 0.5S meter with CTs of matching class, otherwise the system will not achieve the meter's rated accuracy. Sub-meters measure internal consumption only; the utility's own revenue meter remains the reference for your KPLC bill.
This is almost always a wiring issue rather than a faulty meter. The usual causes are a CT fitted the wrong way round (the P1 side should face the supply), CT secondaries swapped between phases so that each current input no longer matches its voltage input, or the wrong CT ratio programmed. Check each phase in turn: current and voltage on the same phase should give a positive kW and a sensible power factor. Short the CT secondaries before disturbing any CT wiring.
A standard RS-485 segment supports 32 unit loads; some devices present a fraction of a unit load, allowing more, so check the datasheets. Modbus allows addresses 1 to 247, and each device on the line needs a unique one. Wire the devices in a daisy chain, not a star, use twisted-pair cable, terminate both ends of the line and set every device to the same baud rate and parity. For longer runs or more devices, add a repeater or split the network across gateways.
It watches the three-phase supply and opens an output contact when something goes wrong: loss of a phase, reversed phase sequence, voltage outside a set band, or, on some models, excessive unbalance. The contact is wired into the motor contactor coil circuit so the motor stops before it overheats or runs backwards. These relays are common on pumps, compressors and conveyors fed from supplies with frequent dips. Products in our range include the VPR-3P, VPR 22 and VPR-126.
An RCCB (IEC 61008-1) detects residual current and breaks the circuit itself; it is a self-contained DIN-rail device, typically rated up to 125 A. An earth leakage relay, such as the ELR 63, only detects: it uses a separate core-balance CT around the live conductors and trips a contactor or a breaker fitted with a shunt trip. That lets it protect large feeders and motors, often with adjustable sensitivity and time delay for coordination. Modular residual current devices of this kind are covered by IEC 60947-2 Annex M.